Practice mode Chemical Engineering

A process with steady-state gain 1.5 is under proportional control with Kc = 4; what is the offset after a unit set-point step?

Correct answer D. 0.143

Explanation

The closed-loop steady gain is Kc Kp/(1 + Kc Kp) = 6/7, so the output settles at 0.857 and the offset is 1/(1 + Kc Kp) = 0.143. Raising the gain shrinks the offset but cannot remove it, and may destabilise the loop. That limitation is why integral action is added.