A process with steady-state gain 1.5 is under proportional control with Kc = 4; what is the offset after a unit set-point step?
Correct answer D. 0.143
Explanation
The closed-loop steady gain is Kc Kp/(1 + Kc Kp) = 6/7, so the output settles at 0.857 and the offset is 1/(1 + Kc Kp) = 0.143. Raising the gain shrinks the offset but cannot remove it, and may destabilise the loop. That limitation is why integral action is added.
Answer checked How we write and check questions
Discussion