What position does an air-to-open control valve take if its instrument air fails?

Correct answer D. Fully closed

Explanation

An air-to-open valve uses air pressure to open against a spring, so losing air lets the spring close it; it is called fail-closed. Engineers choose the action on safety grounds: a fuel valve fails closed, and a cooling-water valve fails open. Holding the last position needs a dedicated lock-up device.