Practice mode Chemical Engineering

A loop has ultimate gain 6 and ultimate period 2 min; what is the proportional gain of a PID controller by closed-loop Ziegler-Nichols tuning?

Correct answer D. 3.6

Explanation

Ziegler-Nichols closed-loop tuning uses Kc = 0.6 Ku for PID, so Kc = 0.6 x 6 = 3.6. The value 2.7 is 0.45 Ku, for PI, and 3.0 is 0.5 Ku, for P only. For PID the method also sets the integral time at Pu/2 and the derivative time at Pu/8.

Report a problem

Answer checked How we write and check questions

Tip: press A, B, C or D to answer, and N for the next question.

Advertisement

Have a question about this answer?

Your email address will not be published. Required fields are marked *

Links and website addresses are not allowed in comments.